Part Number | TSG-SRF140 | TSG-SRF163 | TSG-SRF1125 |
Article Number | 700015 | 700025 | 700045 |
Nominal System Voltage (Un) | 220 - 240 VAC | ||
Max Continuous Operating Voltage (Uc) | 275 VAC | ||
Stand-off Voltage | 440 VAC | ||
Rated Load Current (IL) | 40 A | 63 A | 125 A |
Voltage Protection Level (Up), L-N |
210 V @ 3 kA 180 V @ 20 kA |
262 V @ 3 kA 247 V @ 20 kA |
413 V @ 3 kA 392 V @ 20 kA |
Max Discharge Current (Imax), Per Mode | 130 kA 8/20 μs | ||
Impulse Current (Iimp) | 50 kA 10/350 μs | ||
Filtering | -40 dB @ 100 kHz | ||
Frequency | 50 – 60 Hz | ||
Heat Dissipation | 13 W | 19 W | |
Input Connection | 50 mm² Max | 8 mm Stud | |
Output Connection | 35 mm² Max | 8 mm stud | |
Distribution System | 1Ph 2W+G | ||
Protection Modes | All modes protected | ||
System Compatibility |
TN-C TN-S TT |
||
Technology |
Triggered Spark Gap In-line series low pass sine wave filter |
||
Enclosure Material | Metal | ||
Enclosure Rating | NEMA® 12 (IP55) | ||
Mounting | Wall mount | ||
Status Indication |
LED Change-over contact |
||
Depth (D) | 170 mm | ||
Height (H) | 400 mm | ||
Width (W) | 300 mm | ||
Unit Weight | 11 kg | 13 kg | |
Complies With |
ANSI®/IEEE® C62.41.2-2002 Cat A, Cat B, Cat C ANSI®/IEEE® C62.41.2-2002 Scenario II, Exposure 3, 100 kA 8/20 μs, 10 kA 10/350 μs |
Back-Up Overcurrent Protection for 40 A and 63 A Rated Units | ||
Supply Rating | Minimum Circuit Breaker Rating | Minimum Fuse Rating |
500 A (10 kAIC Max) | 100 A | 40 A |
750 A (15 kAIC Max) | 100 A | 63 A |
1000 A (20 kAIC Max) | 125 A | 80 A |
2000 A (43 kAIC Max) | 160 A | 100 A |