產品規格
Finish: Tinned
Part Number |
Article Number |
Max Current Rating, IEC |
Max Current Rating, UL/CSA |
Line Side Connection |
Load Side Connection |
Material |
Line Side Max Conductor Size, IEC |
Load Side Max Conductor Size, IEC |
Max Working Voltage, IEC (Ui) |
Max Working Voltage, UL (Vin) |
Certifications |
569010 |
80 A |
85 A |
Cable |
6 Cables |
Copper, Thermoplastic |
16 mm² |
16 mm² |
1,000 VAC/DC |
600 V |
CSA, cURus, EAC, RoHS |
|
569020 |
125 A |
150 A |
Cable |
7 Cables |
Copper, Thermoplastic |
35 mm² |
16 mm² |
1,000 VAC/DC |
600 V |
CSA, cURus, EAC, RoHS |
|
569030 |
160 A |
200 A |
Cable |
7 Cables |
Copper, Thermoplastic |
70 mm² |
16 mm² |
1,000 VAC/DC |
600 V |
CSA, cURus, EAC, RoHS |
|
569040 |
250 A |
255 A |
Cable |
11 Cables |
Copper, Thermoplastic |
120 mm² |
35 mm² |
1,000 VAC/DC |
600 V |
CSA, cURus, EAC, RoHS |
|
569041 |
250 A |
255 A |
Flat Conductor |
6 Cables |
Copper, Thermoplastic |
70 mm² |
16 mm² |
1,000 VAC/DC |
600 V |
cURus, EAC, RoHS |
|
569050 |
400 A |
335 A |
Cable |
11 Cables |
Copper, Thermoplastic |
185 mm² |
35 mm² |
1,000 VAC/DC |
600 V |
CSA, cURus, EAC, RoHS |
|
569252 |
400 A |
335 A |
Cable |
12 Cables |
Aluminum, Thermoplastic |
185 mm² |
10 mm² |
1,000 VAC, 1,500 VDC |
1,000 VAC/DC |
CSA, cURus, EAC, RoHS |
|
569052 |
400 A |
335 A |
Cable |
12 Cables |
Copper, Thermoplastic |
185 mm² |
10 mm² |
1,000 VAC, 1,500 VDC |
1,000 VAC/DC |
CSA, cURus, EAC, RoHS |
|
569251 |
400 A |
400 A |
2 Cables |
12 Cables |
Aluminum, Thermoplastic |
95 mm² |
10 mm² |
1,000 VAC, 1,500 VDC |
1,000 VAC/DC |
CSA, cURus, EAC, RoHS |
|
569051 |
400 A |
400 A |
2 Cables |
12 Cables |
Copper, Thermoplastic |
95 mm² |
10 mm² |
1,000 VAC, 1,500 VDC |
1,000 VAC/DC |
CSA, cURus, EAC, RoHS |
|
569060 |
500 A |
335 A |
Flat Conductor |
11 Cables |
Copper, Thermoplastic |
185 mm² |
35 mm² |
1,000 VAC/DC |
600 V |
cURus, EAC, RoHS |
|
569201 |
500 A |
380 A |
Cable |
6 Cables |
Aluminum, Thermoplastic |
240 mm² |
50 mm² |
1,000 VAC, 1,500 VDC |
1,000 VAC/DC |
UL |
|
569202 |
500 A |
475 A |
Flat Conductor |
6 Cables |
Aluminum, Thermoplastic |
100 mm² |
50 mm² |
1,000 VAC, 1,500 VDC |
1,000 VAC/DC |
UL |
|
569204 |
500 A |
490 A |
Flat Conductor |
9 Cables |
Aluminum, Thermoplastic |
100 mm² |
16 mm² |
1,000 VAC, 1,500 VDC |
1,000 VAC/DC |
UL |
|
569206 |
500 A |
500 A |
Flat Conductor |
12 Cables |
Aluminum, Thermoplastic |
100 mm² |
16 mm² |
1,000 VAC, 1,500 VDC |
1,000 VAC/DC |
UL |
|
569203 |
630 A |
420 A |
Cable |
9 Cables |
Aluminum, Thermoplastic |
300 mm² |
16 mm² |
1,000 VAC, 1,500 VDC |
1,000 VAC/DC |
UL |
|
569205 |
630 A |
670 A |
2 Cables |
12 Cables |
Aluminum, Thermoplastic |
185 mm² |
16 mm² |
1,000 VAC, 1,500 VDC |
1,000 VAC/DC |
UL |
|
569208 |
800 A |
670 A |
Flat Conductor |
12 Cables |
Aluminum, Thermoplastic |
240 mm² |
16 mm² |
1,000 VAC, 1,500 VDC |
1,000 VAC/DC |
UL |
|
569207 |
1,000 A |
760 A |
2 Cables |
12 Cables |
Aluminum, Thermoplastic |
240 mm² |
16 mm² |
1,000 VAC, 1,500 VDC |
1,000 VAC/DC |
UL |
|
569210 |
1,000 A |
840 A |
Flat Conductor |
9 Cables |
Aluminum, Thermoplastic |
240 mm² |
70 mm² |
1,000 VAC, 1,500 VDC |
1,000 VAC/DC |
UL |
|
569209 |
1,250 A |
950 A |
2 Cables |
9 Cables |
Aluminum, Thermoplastic |
400 mm² |
70 mm² |
1,000 VAC, 1,500 VDC |
1,000 VAC/DC |
UL |
Design Guideline for Distribution Blocks, Power Blocks and Power Terminals |
||||||||||
Derating according to Ambient* Temperature (°C) to maintain working temperature of 85°C |
||||||||||
Ambient Temperature (°C) |
30° |
35° |
40° |
45° |
50° |
55° |
60° |
65° |
70° |
75° |
Derating Coefficient (d) |
1 |
1 |
1 |
0.94 |
0.88 |
0.82 |
0.75 |
0.67 |
0.58 |
0.47 |
*environment around the terminal blocks inside the enclosure |
Increase the number of outputs with one input using a jumper on blocks with a Max Current Rating, IEC up to 160 A.
Blocks with 1,000 VAC/DC Max Working Voltage, UL are ideal for solar applications.